p2119[0...19]
Change message type type / Change type type
All objects
Can be changed: U, T
Data type: Integer16
P-Group: Messages
Not for motor type: -
Min
1
Description:
Sets the message type for the selected fault or alarm.
Value:
1:
2:
3:
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
r2120
CO: Sum of fault and alarm buffer changes / Sum buffer changed
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency:
Refer to: r0944, r2121
r2121
CO: Counter alarm buffer changes / Alrm buff changed
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
This counter is incremented every time the alarm buffer changes.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125
r2122[0...63]
Alarm code / Alarm code
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the number of alarms that have occurred.
Dependency:
Refer to: r2110, r2123, r2124, r2125, r2134, r2145, r2146, r3121, r3123
Notice:
The properties of the alarm buffer should be taken from the corresponding product documentation.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Fault (F)
Alarm (A)
No message (N)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 4
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
-
543