Siemens G130 List Manual page 361

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p1262[0...n]
Bypass dead time / Bypass t_dead
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: -
Not for motor type: RESM
Min
0.000 [s]
Description:
Sets the dead time for non-synchronized bypass.
Note:
This parameter is used to define the changeover time of the contactors. It should not be shorter than the de-
magnetizing time of the motor (p0347).
The total changeover time for the bypass is based on the total of p1262 plus the OFF time for the relevant switch
(p1274[x]).
p1263
Debypass delay time / Debypass t_del
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: -
Not for motor type: RESM
Min
0.000 [s]
Description:
Sets the delay time to switch back to converter operation for a non-synchronized bypass.
p1264
Bypass delay time / Bypass t_del
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: -
Not for motor type: RESM
Min
0.000 [s]
Description:
Sets the delay time for switching to line operation for a non-synchronized bypass.
p1265
Bypass speed threshold / Bypass n_thresh
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: -
Not for motor type: REL, RESM
Min
0.00 [rpm]
Description:
Sets the speed threshold to activate the bypass.
Note:
When selecting p1260 = 3 and p1267.1 = 1, the bypass is automatically activated when this speed is reached.
p1266
BI: Bypass control command / Bypass command
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: RESM
Min
-
Description:
Sets the signal source for the control command to the bypass.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: CALC_MOD_REG
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
20.000 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
300.000 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
300.000 [s]
Calculated: -
Dyn. index: -
Unit group: 3_1
Scaling: p2000
Max
210000.00 [rpm]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.000 [s]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.000 [s]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.000 [s]
Access level: 2
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
1480.00 [rpm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
361

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents