2 Parameters
2.2 List of parameters
r9748[0...63]
SI message time received in milliseconds / SI t_msg recv ms
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the relative system runtime in milliseconds when the safety message occurred.
Dependency:
Refer to: r9744, r9747, r9749, p9752, r9753, r9754, r9755, r9756
r9749[0...63]
SI message value / SI msg_value
VECTOR_G
Can be changed: -
Data type: Integer32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the additional information about the safety message that occurred (as integer number).
Dependency:
Refer to: r9744, r9747, r9748, p9752, r9753, r9754, r9755, r9756
r9750[0...63]
SI diagnostic attributes / SI diag_attr
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the diagnostic attributes of the safety messages that have occurred.
Bit field:
Bit
00
15
16
17
18
19
20
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the SI message buffer and the assignment of the indices is shown in r9747.
For bits 20 ... 16:
Bits 20, 19, 18, 17, 16 = 0, 0, 0, 0, 0 --> PROFIdrive message class 0: not assigned
Bits 20, 19, 18, 17, 16 = 0, 0, 0, 0, 1 --> PROFIdrive message class 1: hardware fault/software error
Bits 20, 19, 18, 17, 16 = 0, 0, 0, 1, 0 --> PROFIdrive message class 2: line fault
Bits 20, 19, 18, 17, 16 = 0, 0, 0, 1, 1 --> PROFIdrive message class 3: supply voltage fault
Bits 20, 19, 18, 17, 16 = 0, 0, 1, 0, 0 --> PROFIdrive message class 4: DC link fault
Bits 20, 19, 18, 17, 16 = 0, 0, 1, 0, 1 --> PROFIdrive message class 5: power electronics faulted
Bits 20, 19, 18, 17, 16 = 0, 0, 1, 1, 0 --> PROFIdrive message class 6: overtemperature electronic components
Bits 20, 19, 18, 17, 16 = 0, 0, 1, 1, 1 --> PROFIdrive message class 7: ground fault/phase fault detected
Bits 20, 19, 18, 17, 16 = 0, 1, 0, 0, 0 --> PROFIdrive message class 8: motor overload
Bits 20, 19, 18, 17, 16 = 0, 1, 0, 0, 1 --> PROFIdrive message class 9: communication error to the higher-level control
Bits 20, 19, 18, 17, 16 = 0, 1, 0, 1, 0 --> PROFIdrive message class 10: safe monitoring channel has identified an
error
Bits 20, 19, 18, 17, 16 = 0, 1, 0, 1, 1 --> PROFIdrive message class 11: incorrect position actual value/speed actual
value or not available
Bits 20, 19, 18, 17, 16 = 0, 1, 1, 0, 0 --> PROFIdrive message class 12: internal (DRIVE-CLiQ) communication error
990
Signal name
Hardware replacement recommended
Message has gone
PROFIdrive fault class bit 0
PROFIdrive fault class bit 1
PROFIdrive fault class bit 2
PROFIdrive fault class bit 3
PROFIdrive fault class bit 4
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
High
High
High
High
High
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
Low
Low
Low
Low
Low
SINAMICS G130/G150
FP
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents