2 Parameters
2.2 List of parameters
r1593[0...1]
CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Arms]
Description:
Display and connector output for the output of the field weakening controller (synchronous motor) or the output of the
flux controller (separately excited synchronous motor, induction motor).
Index:
[0] = PI output
[1] = I output
p1594[0...n]
Field-weakening controller P gain / Field_ctrl Kp
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, SESM, REL
Min
0.00
Description:
Sets the P gain of the field-weakening controller.
p1595[0...n]
Field weakening controller additional setpoint / Field_ctr add_setp
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: REL
Min
-80.00 [%]
Description:
Sets an additional setpoint for the field weakening controller.
The value refers to the dynamic voltage reserve (p1574).
Note:
For a value equal to zero, the field weakening controller is activated when the maximum voltage, calculated with the
average value of the DC link voltage - and limited using p1575 - is reached.
Positive values mean that the field weakening controller intervenes later.
Negative values cause the field weakening controller to intervene earlier, so that the voltage can move away from the
modulation depth limit.
p1596[0...n]
Field weakening controller integral-action time / Field_ctrl Tn
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
10 [ms]
Description:
Sets the integral-action time of the field-weakening controller.
422
Calculated: -
Dyn. index: -
Unit group: 6_2
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1000.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
50.00 [%]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000 [ms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: 6723, 6724,
6726
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
Access level: 4
Func. diagram: 6724
Unit selection: -
Expert list: 1
Factory setting
0.00
Access level: 4
Func. diagram: 6726
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 3
Func. diagram: 6723, 6724
Unit selection: -
Expert list: 1
Factory setting
50 [ms]
SINAMICS G130/G150