2.2 List of parameters
p2186[0...n]
Load monitoring torque threshold 1 lower / M_thresh 1 lower
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [Nm]
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
p2187[0...n]
Load monitoring torque threshold 2 upper / M_thresh 2 upper
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [Nm]
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
p2188[0...n]
Load monitoring torque threshold 2 lower / M_thresh 2 lower
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [Nm]
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
p2189[0...n]
Load monitoring torque threshold 3 upper / M_thresh 3 upper
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [Nm]
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2189 > p2190
Refer to: p2184, p2190
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
558
Calculated: -
Dyn. index: DDS, p0180
Unit group: 7_1
Scaling: -
Max
20000000.00 [Nm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 7_1
Scaling: -
Max
20000000.00 [Nm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 7_1
Scaling: -
Max
20000000.00 [Nm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 7_1
Scaling: -
Max
20000000.00 [Nm]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
0.00 [Nm]
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
10000000.00 [Nm]
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
0.00 [Nm]
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
10000000.00 [Nm]