p4671 = 0:
The two signals on a track are evaluated differentially.
p4671 = 1:
Only the non-inverted signal on a track is evaluated.
p4671 = 2:
Only the inverted signal on a track is evaluated.
p4671 = 3:
Only the non-inverted signal on a track (high resolution) is evaluated.
p4672[0...n]
Analog sensor channel A voltage at actual value zero / Ana_sens A U at 0
VECTOR_G, ENC
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-10.0000 [V]
Description:
Sets the voltage when the connected sensor is at actual value zero.
At this voltage channel A supplies an actual value of zero.
p4673[0...n]
Analog sensor channel A voltage per encoder period / Ana_sens A U/per
VECTOR_G, ENC
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-10.0000 [V]
Description:
Sets the output voltage range to be mapped for the connected analog sensor.
The voltage range is determined by the following parameters:
- p4672 (voltage at actual value 0)
- p4673 (voltage per encoder period)
Note:
The minimum actual value which can be mapped is equal to p4672 - p4673/2.
The maximum actual value which can be mapped is equal to p4672 + p4673/2.
p4674[0...n]
Analog sensor channel B voltage at actual value zero / Ana_sens B U at 0
VECTOR_G, ENC
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-10.0000 [V]
Description:
Sets the voltage when the connected sensor is at actual value zero.
At this voltage channel B supplies an actual value of zero.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
10.0000 [V]
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
10.0000 [V]
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
10.0000 [V]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0000 [V]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6.0000 [V]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0000 [V]