r0330[0...n]
Rated motor slip / Mot slip_rated
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PMSM, SESM, REL,
RESM
Min
- [Hz]
Description:
Displays the rated motor slip.
Dependency:
The rated slip is calculated from the rated frequency, rated speed and number of pole pairs.
Refer to: p0310, p0311, r0313
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
r0331[0...n]
Actual motor magnetizing current/short-circuit current / Mot I_mag_rtd act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: SESM, REL
Min
- [Arms]
Description:
Induction motor:
Displays the rated magnetizing current from p0320.
For p0320 = 0, the internally calculated magnetizing current is displayed.
Synchronous motor:
Displays the rated short-circuit current from p0320.
Dependency:
If p0320 was not entered, then the parameter is calculated from the rating plate parameters.
Note:
In the case of multi-motor operation r0331 is increased by the factor p0306 compared to p0320.
r0332[0...n]
Rated motor power factor / Mot cos phi rated
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PMSM, REL
Min
-
Description:
Displays the rated power factor for induction motors.
For IEC motors, the following applies (p0100 = 0):
For p0308 = 0, the internally calculated power factor is displayed.
For p0308 > 0, this value is displayed.
For NEMA motors, the following applies (p0100 = 1, 2):
For p0309 = 0, the internally calculated power factor is displayed.
For p0309 > 0, this value is converted into the power factor and displayed.
Dependency:
If p0308 is not entered, the parameter is calculated from the rating plate parameters.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
- [Hz]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
- [Arms]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 3
Func. diagram: 5722, 6722,
6724
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-