2 Parameters
2.2 List of parameters
Note:
For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
p1122[0...n]
BI: Bypass ramp-function generator / Bypass RFG
VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for bypassing the ramp generator (ramp-up and ramp-down times = 0).
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
The bypass is kept for OFF1/OFF3.
Note:
For VECTOR in encoderless operation, it is not permissible that the ramp-function generator is bypassed.
p1130[0...n]
Ramp-function generator initial rounding-off time / RFG t_start_round
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [s]
Description:
Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note:
Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
p1131[0...n]
Ramp-function generator final rounding-off time / RFG t_end_delay
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [s]
Description:
Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
Note:
Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
p1134[0...n]
Ramp-function generator rounding-off type / RFG round-off type
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Setpoints
Not for motor type: -
Min
0
Description:
Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function
generator.
Value:
0:
1:
Dependency:
No effect up to initial rounding-off time (p1130) > 0 s.
Note:
p1134 = 0 (continuous smoothing)
If the setpoint is reduced while ramping-up, initially a final rounding-off is carried out and then the ramp-up
completed. During the final rounding-off, the output of the ramp-function generator continues to go in the direction of
the previous setpoint (overshoot). After the final rounding-off has been completed, the output goes toward the new
setpoint.
326
Cont smoothing
Discont smoothing
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
30.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
30.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2505
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3070
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 2
Func. diagram: 3070
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 2
Func. diagram: 3070
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150