2 Parameters
2.2 List of parameters
BI: p0854 = 1 signal
Master control by PLC.
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then binector input p0854 should be set to 1.
If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies
regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
p0855[0...n]
BI: Unconditionally release holding brake / Uncond open brake
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "unconditionally open holding brake".
Dependency:
Refer to: p0858
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The signal via BI: p0858 (unconditionally close holding brake) has a higher priority than via BI: p0855 (unconditionally
open holding brake).
p0856[0...n]
BI: Enable speed controller / n_ctrl enable
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable speed controller" (r0898.12).
0 signal: Set the I component and speed controller output to zero.
1 signal: Enable speed controller.
Dependency:
Refer to: r0898
Note:
If "enable speed controller" is withdrawn, then an existing brake will be closed.
If "enable speed controller" is withdrawn, the pulses are not suppressed.
p0857
Power unit monitoring time / PU t_monit
VECTOR_G, B_INF
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
100.0 [ms]
Description:
Sets the monitoring time for the power unit.
The following applies for infeeds and drives:
The monitoring time is started after an 0/1 edge of the ON/OFF1 command. If the power unit does not return a
READY signal within the monitoring time, then fault F06000 (infeeds) or F07802 (drives) is output.
For drives, the following also applies:
After the pulse enable (operation enabled, p0852), the monitoring time is re-started. If the infeed does not signal
ready to the drive within the monitoring time (using BI: p0864 of the drive), fault F07840 is initiated.
280
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60000.0 [ms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2501, 2701,
2707
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2501, 2701,
2707
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: 8760, 8864,
8964
Unit selection: -
Expert list: 1
Factory setting
6000.0 [ms]
SINAMICS G130/G150