N8: Pm Motor Control Tuning - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.12 n: Special Adjustment
No.
Name
(Hex.)
n7-07
Speed Calculation Gain1
(3117)
Expert
n7-08
Speed Calculation Gain2
(3118)
Expert
n7-10
Pull-in Current
Switching Speed
(311A)
Expert
n7-17
Resistance
TemperatureCorrection
(3122)
n7-19
Flux Error
Compensation Gain
(3128)
Expert

n8: PM Motor Control Tuning

No.
Name
(Hex.)
n8-01
Pole Position Detection
Current
(0540)
Expert
n8-02
Pole Alignment Current
Level
(0541)
Expert
n8-11
Observer Calculation
Gain 2
(054A)
n8-14
Polarity Compensation
Gain 3
(054D)
Expert
n8-15
Polarity Compensation
Gain 4
(054E)
Expert
n8-21
Motor Back-EMF (Ke)
Gain
(0554)
Expert
n8-35
Initial Pole Detection
Method
(0562)
n8-36
HFI Frequency Level for
L Tuning
(0563)
n8-37
HFI Voltage Amplitude
Level
(0564)
Expert
398
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed calculation gain during usual operation. Usually it is not necessary to
change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the speed calculation gain during a speed search.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the speed range to operate with the pull-in current command. Drive rated frequency
= 100% value. If there is a large quantity of oscillation when you operate in the low
speed range, increase the setting value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to adjust for changes in the motor resistance value caused by changes
in the temperature.
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for magnetic flux compensation. Usually it is not necessary to change this
setting.
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets, as a percentage, the Initial Rotor Position Estimated Current, taking the E5-03
[Motor Rated Current (FLA)] as the 100% value. Usually it is not necessary to change
this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the current at the time of polar attraction as a percentage where E5-03 [motor rated
current] is 100%. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets how the drive detects the position of the rotor when the motor starts.
Note:
• When you use an SPM motor, set n8-35 = 0. When you use an IPM motor, set n8-
35 = 0 to 2.
• When you set n8-35 = 1, do High Frequency Injection Auto-Tuning.
0 : Pull-in
1 : High Frequency Injection
2 : Pulse Injection
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the injection frequency for high frequency injection.
Note:
• Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-
57 = 1 [HFI Overlap Selection = Enabled] to enable this parameter.
• The drive automatically calculates this value when High Frequency Injection
Auto-Tuning completes successfully.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the high frequency injection amplitude as a percentage where 200 V = 100% for
200 V class drives and 400 V = 100% for a 400 V class drives. Usually it is not
necessary to change this setting.
Note:
• Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-
57 = 1 [HFI Overlap Selection = Enabled] to enable this parameter.
• The drive automatically calculates this value when High Frequency Injection
Auto-Tuning completes successfully.
Default
(Range)
15.0 Hz
(1.0 - 50.0 Hz)
25.0 Hz
(1.0 - 50.0 Hz)
10.0%
(0.0 - 100.0%)
1
(0 to 2)
5000%
(0 - 50000%)
Default
(Range)
50%
(0 - 100%)
80%
(0 - 150%)
Determined by n8-72
(0.0 - 1000.0)
1.000
(0.000 - 10.000)
0.500
(0.000 - 10.000)
0.90
(0.80 - 1.00)
Determined by A1-02
(0 - 2)
500 Hz
(200 - 1000 Hz)
20.0%
(0.0 - 50.0%)
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
719
719
719
719
719
Ref.
720
720
720
720
720
720
721
721
721

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents