3.10 Control I/O Connections
n
Using External Power Supply (Sink Mode)
The high voltage level of the pulse output signal depends on the external voltage applied. The voltage must be between 12
and 15 Vdc. The load resistance must be adjusted so that the current is lower than 16 mA.
External Power Supply (V)
12 to 15 Vdc ±10%
u

Terminal A2 Input Signal Selection

Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained in
Table
3.11. Set parameter H3-09 accordingly as shown in
Board on page 67
for locating switch S1.
Note: If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
Setting
V (left position)
I (right position)
No.
Parameter Name
H3-09
Terminal A2 signal level selection
u

Terminal A3 Analog/PTC Input Selection

Terminal A3 can be configured either as multi-function analog input or as PTC input for motor thermal overload protection.
Use switch S4 to select the input function as described in
Board on page 67
for locating switch S4.
Setting
AI (lower position) (default)
PTC (upper position)
70
External Power Supply
MP
AC
Figure 3.22 Pulse Output Connection Using External Voltage Supply
Table 3.11 DIP Switch S1 Settings
Current input (4 to 20 mA or 0 to 20 mA): default setting
Table 3.12 Parameter H3-09 Details
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
Table 3.13 DIP Switch S4 Settings
Analog input for the function selected in parameter H3-06
PTC input. Parameter H3-06 must be set to E (PTC input)
Load Impedance
Sink Current
Table
3.12.
Refer to Switches and Jumpers on the Terminal
Description
Voltage input (-10 to +10 V)
Description
Table
3.13.
Refer to Switches and Jumpers on the Terminal
Description
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Load Impedance (kΩ)
1.0 kΩ or higher
Setting
Range
0 to 3
Default
Setting
2