3 Electrical Installation
Using External Power Supply (Sink Mode)
The high voltage level of the pulse output signal depends on the external voltage applied. The voltage must be between
12 and 15 Vdc. The load resistance must be adjusted so that the current is lower than 16 mA.
External Power Supply (V)
12 to 15 Vdc ±10%
Figure 44

◆ Terminal A2 Analog Input Signal Selection

Terminal A2 Input Signal Selection
Terminal A2 can be used to input either a voltage or a current signal.
When using input A2 as a voltage input, set DIP switch S1 to "V" (left position) and set parameter H3-09 to 0 (0 to 10
Vdc) or to 1 (-10 to 10 Vdc).
To use current input at terminal A2, set the DIP switch S1 to "I" (default setting) and H3-09 = 2 or 3 (4 to 20 mA or 0 to
20 mA).
To set the DIP switch on the terminal board, use an appropriate sized tool with a tip of approximately 0.8 mm in width.
Figure 45
Note: If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create
the frequency reference.
Setting
V (left position)
I (right position) (default)
50
External Power Supply
MP
AC
Figure 44 Pulse Output Connection Using External Voltage Supply
Figure 45 DIP Switch S1
Table 15 DIP Switch S1 Settings
Current input (4 to 20 mA or 0 to 20 mA): default setting
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Load Impedance (kΩ)
1.0 kΩ or higher
Load Impedance
Sink Current
Dip Switch S1
V
YEC_common
Description
Voltage input (-10 to +10 V)
I