10 Drive Start-Up Procedure

Output Terminals

Refer to
Table 10.2
and
Table 10.3
Type
Terminal
N.O. output
MA
(Fault)
Fault Relay
N.C. output
Output
MB
(Fault)
MC
Digital output common
M1
MFDO
(During Run)
M2
M3
MFDO
MFDO
(Zero Speed)
M4
M5
MFDO
(Speed Agree 1)
M6
Type
Terminal
Pulse train output
MP
(Output frequency)
Analog monitor output 1
FM
(Output frequency)
Monitor Output
Analog monitor output 2
AM
(Output current)
AC
Monitor common

External Power Supply Input Terminals

Refer to
Table 10.4
for a list of the functions of the external power supply input terminals.
Type
External Power Supply Input
Terminals

Serial Communication Terminals

Refer to
Table 10.5
for a list of serial communication terminals and functions.
Type
Modbus Communication

Control Circuit Terminal Configuration

The control circuit terminals are in the positions shown in
38
for a list of output terminals and functions.
Table 10.2 Control Circuit Output Terminals
Name (Default)
Table 10.3 Control Circuit Monitor Output Terminals
Name (Default)
Table 10.4 External Power Supply Input Terminals
Terminal
Name (Default)
PS
External 24 V power supply input
AC
External 24 V power supply ground
Table 10.5 Serial Communication Terminals
Terminal
Terminal Name
Communication
MEMOBUS/Modbus communications
D+
input/output (+)
Use an RS-485 cable to connect the drive.
Communication
D-
output (-)
0 V
AC
Shield ground
• Relay output
• 30 Vdc, 10 mA to 1 A
• 250 Vac, 10 mA to 1 A
• Minimum load: 5 V, 10 mA (Reference value)
• Relay output
• 30 Vdc, 10 mA to 1 A
• 250 Vac, 10 mA to 1 A
• Minimum load: 5 V, 10 mA (Reference value)
Note:
Do not set functions that frequently switch ON/OFF to MFDO (M1 to M6) because this will
decrease the performance life of the relay contacts. Yaskawa estimates switching life at
200,000 times (assumes 1 A, resistive load).
32 kHz (maximum)
Refer to "Pulse Train Output" on page
Select voltage or current output.
• 0 V to 10 V/0% to 100%
• -10 V to +10 V/-100% to +100%
• 4 mA to 20 mA (receiver recommended impedance: 250 Ω)
Note:
Select with jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08
[Terminal AM Signal Level Select].
0 V
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
0 V
Function (Signal Level)
Note:
Set DIP switch S2 to ON to enable the
termination resistor in the last drive in a
MEMOBUS/Modbus network.
Figure
10.1.
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Function (Signal Level)
Function (Signal Level)
44
for more information.
Function
• RS-485
• MEMOBUS/Modbus communication protocol
• Maximum 115.2 kbps