Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to
S5), and multi-function digital outputs (MA, MB). The default is called out next to each
terminal in
Figure
3.10.
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being
wired. Operating a drive with untested control circuits could result in death or serious injury.
WARNING! Confirm the drive I/O signals and external sequence before starting test run. Failure to comply
may result in death or serious injury.
NOTICE: Do not switch an input contactor more often than once every 30 minutes. Improper equipment
sequencing could shorten useful life of the drive electrolytic capacitors and circuit relays. Normally the drive
I/O should be used to stop and start the motor.
n
Input Terminals
Type
No.
Terminal Name (Function)
S1 Multi-function input 1 (Closed: Forward
run, Open: Stop)
Multi-function input 2 (Closed: Reverse run,
S2
Open: Stop)
Multi-
S3 Multi-function input 3 (External fault (N.O.)
Function
Digital
S4 Multi-function input 4 (Fault reset)
Inputs
Multi-function input 5 (Multi-step speed
S5
reference 1)
Multi-function input common (Control
SC
common)
Main
A1 Frequency reference
Frequency
Reference
Input
+V Analog input power supply
AC Frequency reference common
n
Output Terminals
Type
No.
MA N.O. (fault)
Multi-Function
MB N.C. output (fault)
Digital Output
MC Digital output common
AM Analog monitor output
Monitor Output
AC Monitor common
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Table 3.6 Control Circuit Input Terminals
Table 3.7 Control Circuit Output Terminals
Terminal Name (Function)
3.7 Control Circuit Wiring
Function (Signal Level) Default Setting
24 Vdc, 8 mA
Note: Drive preset to sinking mode. When using
source mode, set DIP switch S3 to allow for a 24 Vdc
(±10%) external power supply.
Sourcing Mode Switch on page
Sequence common
Input voltage or input current (Selected by DIP switch
S1 and H3-01) 0 to +10 Vdc (20 kΩ),
Resolution: 1/1000
4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω),
Resolution: 1/500
+10.5 Vdc (max allowable current 20 mA)
0 Vdc
Function (Signal Level) Default Setting
Digital output
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA (reference value)
0 to 10 Vdc (2 mA or less) Resolution: 1/256
0 V
Refer to Sinking/
60.
3
55