2 Parameters
2.2 List of parameters
If value = 2:
Components of a drive object in a project generated offline and set to this value must never be inserted in the actual
topology from the very start. This means that the components are marked to be bypassed in the DRIVE-CLiQ line.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
p0105
Activate/deactivate drive object / DO act/deact
TM31
Can be changed: T
Data type: Integer16
P-Group: Closed-loop control
Not for motor type: -
Min
0
Description:
Setting to activate/deactivate a drive object.
Value:
0:
1:
2:
Recommendation:
After inserting all of the components of a drive object, before activating, first wait for Alarm A01316.
Dependency:
Refer to: r0106
Refer to: A01314
Warning:
A drive that is moved by simulating the inputs of a Terminal Module is brought to a standstill while this parameter is
being changed over.
Notice:
The following applies when activating:
If components are inserted for the first time and the appropriate drive object is activated, then the drive system is
automatically booted. To do this, the pulses of all of the drive objects must be suppressed.
Note:
For value = 0, 2:
When a drive object is deactivated it no longer outputs any errors.
If value = 0:
All components of the drive object were completely commissioned and are deactivated using this value. They can be
removed from the DRIVE-CLiQ without any error.
If a component has been deactivated, only the component with the correct serial number may be inserted, or none at
all.
If value = 1:
All components of the drive object must be available for error-free operation.
If value = 2:
Components of a drive object in a project generated offline and set to this value must never be inserted in the actual
topology from the very start. This means that the components are marked to be bypassed in the DRIVE-CLiQ line.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
p0105
Activate/deactivate drive object / DO act/deact
TM54F_MA,
Can be changed: T
TM54F_SL
Data type: Integer16
P-Group: Closed-loop control
Not for motor type: -
Min
0
Description:
Setting to activate/deactivate a drive object.
Value:
0:
1:
2:
Recommendation:
After inserting all of the components of a drive object, before activating, first wait for Alarm A01316.
76
Deactivate drive object
Activate drive object
Drive object deactivate and not present
Deactivate drive object
Activate drive object
Drive object deactivate and not present
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1