r0026
CO: DC link voltage smoothed / Vdc smooth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [V]
Description:
Displays the smoothed actual value of the DC link voltage.
Dependency:
Refer to: r0070
Notice:
For SINAMICS S120 AC Drive (AC/AC) the following applies:
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM340) a valid measured value is not
supplied. In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the
display parameter.
Note:
SERVO, VECTOR: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0026
CO: DC link voltage smoothed / Vdc smooth
B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [V]
Description:
Displays the smoothed actual value of the DC link voltage.
Dependency:
Refer to: r0070
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note:
A_INF, B_INF, S_INF: smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0027
CO: Absolute actual current smoothed / I_act abs val smth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Displays the smoothed absolute actual current value.
Dependency:
Refer to: r0068
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note:
A_INF, S_INF, VECTOR: Smoothing time constant = 300 ms
SERVO: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2001
Max
- [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2001
Max
- [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2002
Max
- [Arms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 6799, 8750,
8850, 8950
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 2
Func. diagram: 5730, 6799,
8750, 8850, 8950
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 2
Func. diagram: 5730, 6799,
8850, 8950
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
49