r0030
Current actual value torque-generating smoothed / Iq_act smooth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Displays the smoothed torque-generating actual current.
Dependency:
Refer to: r0078
Note:
SERVO: Smoothing time constant = 100 ms
VECTOR: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The following applies for SERVO:
The torque-generating current actual value is available smoothed (r0030 with 100 ms, r0078[1] with p0045) and
unsmoothed (r0078[0]).
The following applies for VECTOR:
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
r0031
Actual torque smoothed / M_act smooth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Nm]
Description:
Displays the smoothed torque actual value.
Dependency:
Refer to: r0080
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque actual value is available smoothed (r0031) and unsmoothed (r0080).
r0032
CO: Active power actual value smoothed / P_actv_act smth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [kW]
Description:
Display and connector output for the smoothed actual value of the active power.
Dependency:
Refer to: r0082
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note:
Significance for the drive: Power output at the motor shaft
Significance for the infeed: Line power drawn
For A_INF, B_INF and S_INF the following applies:
The active power is available smoothed (r0032 with 300 ms) and unsmoothed (r0082).
The following applies for SERVO:
The active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed (r0082[0]).
For VECTOR and VECTORMV, the following applies:
The active power is available smoothed (r0032 with 100 ms) and unsmoothed (r0082).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Unit group: 7_1
Scaling: p2003
Max
- [Nm]
Calculated: -
Dyn. index: -
Unit group: 14_10
Scaling: r2004
Max
- [kW]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 5730, 6799
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
Access level: 2
Func. diagram: 5730, 6799
Unit selection: p0505
Expert list: 1
Factory setting
- [Nm]
Access level: 2
Func. diagram: 5730, 6799,
8750, 8850, 8950
Unit selection: p0505
Expert list: 1
Factory setting
- [kW]
51