Siemens G130 List Manual page 54

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
r0035
CO: Temperature input / Temp_input
B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [°C]
Description:
Displays the temperature currently measured at X21 (booksize) or X41 (chassis).
For a BLM with internal Braking Module, a bimetallic sensor must be connected up to monitor the temperature of the
braking resistor. The temperature sensor type is indicated using p0601 and cannot be changed for the existing
internal Braking Module.
Temperature within permissible limit values: r0035 = -50°C
Temperature outside the permissible limit values: r0035 = 250°C
Dependency:
Refer to: F06907, F06908
Notice:
The function in r0192.11 must be available in order to obtain a correct display.
Note:
For r0035 equal to -200.0 °C, the following applies:
- "no sensor" selected in p0601!
For r0035 equal to -300.0 °C, the following applies:
- a KTY/PT1000 is selected in p0601 but is not connected!
- the temperature display is not valid (temperature sensor error)!
r0036
CO: Power unit overload I2t / PU overload I2t
VECTOR_G, B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the power unit overload determined using the I2t calculation.
A current reference value is defined for the I2t monitoring of the power unit. It represents the current that can be
conducted by the power unit without any influence of the switching losses (e.g. the continuously permissible current
of the capacitors, inductances, busbars, etc.).
If the I2t reference current of the power unit is not exceeded, then an overload (0 %) is not displayed.
In the other case, the degree of thermal overload is calculated, whereby 100% results in a trip.
Dependency:
Refer to: p0290, p0294
Refer to: F30005
r0037[0...1]
Control Unit temperature / CU temp
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Displays, signals
CU_G150_DP
Not for motor type: -
Min
- [°C]
Description:
Displays the measured Control Unit temperature.
An appropriate message is output when the permitted operating temperature is exceeded.
Index:
[0] = Actual measured value
[1] = Maximum measured value
Dependency:
Refer to: A01009
Notice:
Only for internal Siemens troubleshooting.
Note:
The value of -200 indicates that there is no measuring signal.
54
Calculated: -
Dyn. index: -
Unit group: 21_1
Scaling: p2006
Max
- [°C]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2006
Max
- [°C]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 8750
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]
Access level: 3
Func. diagram: 8021
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [°C]
SINAMICS G130/G150