D2: Reference Limits - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

No.
Name
(Hex.)
d1-12
Reference 12
(028D)
RUN
d1-13
Reference 13
(028E)
RUN
d1-14
Reference 14
(028F)
RUN
d1-15
Reference 15
(0290)
RUN
d1-16
Reference 16
(0291)
RUN
d1-17
Jog Reference
(0292)
RUN

d2: Reference Limits

No.
Name
(Hex.)
d2-01
Frequency Reference
Upper Limit
(0289)
d2-02
Frequency Reference
Lower Limit
(028A)
d2-03
Analog Frequency Ref
Lower Limit
(0293)
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [Frequency Display Unit
Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-
03 = 1 [0.01% (100% = E1-04)].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit
Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-
03 = 1 [0.01% (100% = E1-04)].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit
Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-
03 = 1 [0.01% (100% = E1-04)].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [Frequency Display Unit
Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-
03 = 1 [0.01% (100% = E1-04)].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [Frequency Display Unit
Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-
03 = 1 [0.01% (100% = E1-04)].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Jog frequency reference in the units from o1-03 [Frequency Display Unit
Selection]. Set H1-xx = 6 [MFDI Function Select = Jog Reference Selection] to use the
Jog frequency reference.
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-
03 = 1 [0.01% (100% = E1-04)].
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets maximum limit for all frequency references. The maximum output frequency is
100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Motor Max Revolutions]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets minimum limit for all frequency references. The maximum output frequency is
100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Motor Max Revolutions]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the lower limit for the master frequency reference (the first frequency of the multi-
step speed reference) as a percentage. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
11.7 d: Reference Settings
Default
Ref.
(Range)
0.00 Hz
544
(0.00 - 590.00 Hz)
0.00 Hz
545
(0.00 - 590.00 Hz)
0.00 Hz
545
(0.00 - 590.00 Hz)
0.00 Hz
545
(0.00 - 590.00 Hz)
0.00 Hz
545
(0.00 - 590.00 Hz)
6.00 Hz
545
(0.00 - 590.00 Hz)
Default
Ref.
(Range)
100.0%
546
(0.0 - 110.0%)
0.0%
546
(0.0 - 110.0%)
0.0%
546
(0.0 - 110.0%)
11
353