5.11 Auto-Tuning

5.11 Auto-Tuning

Auto-Tuning automatically sets and tunes parameters required for motor operation.

Types of Auto-Tuning

u
There are three types of Auto-Tuning.
Type
Rotational Auto-Tuning for V/
f Control
Rotational Auto-Tuning for
OLV Control
Stationary Auto-Tuning for V/
f and OLV Control Line-to-
Line Resistance Only
Note: Auto-Tuning cannot be performed on permanent magnet motors (IPM, SPM, etc.).
u

Auto-Tuning Selection

u

Before Auto-Tuning the Drive

Check the items below before Auto-Tuning the drive:
210
Refer to Auto-Tuning Selection on page 92
Setting
Assumes the motor can rotate during the Auto-Tuning process.
T1-01 = 3
Improves torque compensation, slip compensation, energy savings, and speed search
performance.
Assumes the motor can rotate during the Auto-Tuning process
T1-01 = 0
Achieves high-performance motor control
For use when the motor cable exceeds 50 m
The motor cable length has been modified after Auto-Tuning has been previously
T1-01 = 2
performed
When motor capacity and drive capacity differ
Select the Motor Control Mode A1-02
V/f Control
A1-02 = 0
Select a V/f pattern
E1-03
Will the application
allow motor rotation
for Auto-Tuning?
NO
YES
Is the cable
between the motor
and drive longer
than 50 m?
V/f Rotational
YES
Auto-Tuning
(T1-01 = 3)
Stationary Auto-Tuning
for Terminal Resistance Only
(T1-01 = 2)
to select the best type of Auto-Tuning for the application.
Application Conditions and Benefits
START
Open Loop Vector
PM Open Loop Vector Control
A1-02 = 2
NO
connected load
Can the load be
expected to be less
disconnected from
than 30% of the motor
the motor?
YES
YES
NOTICE: Auto-Tuning with
a connected load is possible,
but may result in less than
optimum performance.
NO
Rotational
Select V/f Control
Auto-Tuning
Mode (A1-02 = "0")
(T1-01 = 0)
for the drive.
Note: Manually set parameters
when OLV control is needed.
Run the motor without the load.
Connect the load and run the motor.
Verify system operates as required.
Auto-Tuning finished.
Figure 5.75
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
V/f Control
Open Loop Vector Control
V/f Control, Open Loop Vector Control
A1-02 = 5
Is the total
rating?
NO
Control Mode