S_STW2 Safety control word 2
[2858.2]
Bit No.
0
1 = Deselection STO
1
1 = Deselection SS1
2
1 = Deselection SS2
3
1 = Deselection SOS
4
1 = Deselection SLS
5
Reserved
6
1 = Deselection SLP
7
1/0 = Acknowledgment
Reserved
8
9
1 = Select SLS bit 0
10
1 = Select SLS bit 1
11
Reserved
12
1 = Deselection SDI positive
13
1 = Deselection SDI negative
Reserved
19
SLP position area
Reserved
24
Select gearbox stage bit 0
25
Select gearbox stage bit 1
26
Select gearbox stage bit 2
27
Gearbox stage switchover
28
1 = Deselection SS2E
Reserved
<1> Only for CU310-2.
1
2
DO: SERVO, VECTOR
SI Extended Functions - S_STW2 Safety control word 2, S_ZSW2 Safety status word 2
S_STW2
Meaning
[2858.3]
0 = SLP1
1 = SLP2
3
4
S_ZSW2 Safety status word 2
Bit No.
0
1 = STO or safe pulse cancellation active
[2858.6]
1
1 = SS1 active
[2858.6]
2
1 = SS2 active
[2858.6]
3
1 = SOS active
[2858.6]
4
1 = SLS active
5
Reserved
[2858.6]
6
1 = SLP active
r9722.7
1
7
1 = Internal event
[2858.6]
8
Reserved
[2858.6]
9
Active SLS stage bit 0
[2858.6]
10
Active SLS stage bit 1
11
Reserved
[2858.6]
12
1 = SDI pos active
[2858.6]
13
1 = SDI neg active
14
Reserved
[2858.6]
15
SSM (Speed below limit value)
Reserved
[2858.6]
19
SLP active position area
Reserved
[2858.6]
22
1 = SP valid
[2858.6]
23
1 = Safety referenced
[2070.8]
24
1 = F-DI 0 inactive
[2070.8]
25
1 = F-DI 1 inactive
[2070.8]
26
1 = F-DI 2 inactive
27
Reserved
[2858.6]
28
1 = SS2E active
[2858.6]
29
1 = SOS selected
[2858.6]
30
1 = SLP limit upper maintained
[2858.6]
31
1 = SLP limit lower maintained
5
6
fp_2843_54_eng.vsd
01.04.16 V04.08.00
2 x p9500 (24.00 ms)
S_ZSW2
Meaning
[2858.7]
0 = SLS1
1 = SLS2
2 = SLS3
3 = SLS4
0 = SLP1
1 = SLP2
<1>
<1>
<1>
7
8
Function diagram
- 2843 -
S120/S150/G130/G150

Hide quick links: