Signal sources for ZSW1_BM
Signal
Meaning
ZSW1.0
1 = Ready for switching on
ZSW1.1
1 = Ready for operation
ZSW1.2
1 = Operation enabled
ZSW1.3
1 = Fault present
ZSW1.4
1 = No coast down active (OFF2 inactive)
ZSW1.5
1 = No quick stop active (OFF3 inactive)
ZSW1.6
1 = Switching on inhibited active
ZSW1.7
1 = Alarm present
ZSW1.8
1 = Speed setpoint - actual value deviation within tolerance t_off
ZSW1.9
1 = Control requested
ZSW1.10
1 = f or n comparison value reached/exceeded
ZSW1.11
1 = I, M, or P limit not reached
ZSW1.12
1 = Open the holding brake
ZSW1.13
Reserved
ZSW1.14
Reserved
ZSW1.15
Reserved
<1> Used in telegram 220.
<2> The ZSW1 is generated using the binector-connector converter (BI: p2080[0...15], inversion: p2088[0].0...p2088[0].15)
<3> The drive object is ready to accept data.
1
2
DO: SERVO, VECTOR
PROFIdrive - ZSW1_BM status word, metal industry interconnection
Interconnection
parameters
p2080[0] = r0899.0
p2080[1] = r0899.1
p2080[2] = r2811.0
p2080[3] = r2139.3
p2080[4] = r0899.4
p2080[5] = r0899.5
p2080[6] = r0899.6
p2080[7] = r2139.7
p2080[8] = r2197.7
<3>
p2080[9] = r0899.9
p2080[10] = r2199.1
<4>
p2080[11] = r1407.7
p2080[12] = r0899.12
<6>
<6>
<6>
3
4
[Function diagram]
[Function diagram]
Internal status word
signal source
[2503.7]
[2610]
[2503.7]
[2610]
[2503.7]
[2610]
[2548.7]
[8060]
[2503.7]
[2610]
[2503.7]
[2610]
[2503.7]
[2610]
[2548.7]
[8065]
[2534.7]
[8010]
[2503.7]
[2503]
[2536.7]
[8010]
[5610] [6060]
[2522.7]
<5>
[2503.7]
[2701]
<6>
-
-
<6>
-
<6>
<4> Not for VECTOR U/f.
<5> Only for SINAMICS S120.
<6> Interconnection is not disabled.
5
6
fp_2428_54_eng.vsd
27.06.13 V04.08.00
PROFIdrive sampling time
<1>
Inverted
<2>
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
Function diagram
- 2428 -