Test Eda-External-Device-Alrm - Avaya DEFINITY Server CSI Maintenance Manual

Table of Contents

Advertisement

Maintenance Commands

test eda-external-device-alrm

Use test eda-external-device-alrm to run a hardware diagnostic test on all or
specific port's administered external device alarms. The test PASSES if the
external device is not reporting an external device alarm and FAILS if the external
device is reporting an external device alarm. If you enter a specific port, it must be
administered as an external device alarm port on a maintenance or an analog line
port carrier board.
Action/Object
Qualifier
test
physical
eda-external-
location
device-alrm
all
repeat
clear
schedule
1
Since the "maintenance board" alarm connections connect to control carrier boards that are in unnumbered
slots, the standard port format cannot be used to designate these alarm connections. The special ports Pmajor
and Pminor are used designate the major or minor maintenance board alarm connection for cabinet P. The
major/minor designation specifies the pair of wires, not the alarm level associated with the connection (the
"major" port can be administered as a major, minor or warning alarm and the "minor" port can be administered
as a major, minor or warning alarm).
2
If no alarms are registered against the maintenance object then the test sequence is run only once. The long
clear option forces a clear of all alarms if no errors are encountered during testing. The short clear option only
clears alarms pertinent to tests in the short sequence.
3
See the Report Scheduler and System Printer feature specification for more details.
548
Issue 5 October 2002
Qualifier Description
In addition to the word physical, you
must enter the physical location
(PCSSpp for an administered external
device alarm analog line port).
Tests all administered external device
alarm ports on analog line and
maintenance boards.
How many times each test in the
sequence is repeated (1-100)
This option causes the test sequence
(short or long) to repeat until the alarm (if
any) is cleared or a single test in the
2
sequence fails.
Use the screen to schedule execution of
the command. The command is placed in
the command queue and is executed at
the specified time. The information
displayed by the command is sent to the
system printer instead of the screen.
Examples:
test eda-external-device-alrm all
test eda-external-device-alrm all
schedule
test eda-external-device-alrm physical
1major r 10
test eda-external-device-alrm physical
2c1101 c
Logins
Default
init
Repeat
inads
= 1
craft
1
3
Feature
Interactions
none
555-233-119