Note:
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
For p3900 not equal to 0, at the end of the quick commissioning, this parameter is automatically reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
p0010
TM120 commissioning parameter filter / TM120 com par_filt
TM120
Can be changed: C2(1), T
Data type: Integer16
P-Group: All groups
Not for motor type: -
Min
0
Description:
Sets the parameter filter for commissioning a Terminal Module 120 (TM120).
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Value:
0:
29:
30:
Dependency:
Refer to: p0970
Note:
Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
p0010
TM150 commissioning parameter filter / TM150 com par_filt
TM150
Can be changed: C2(1), T
Data type: Integer16
P-Group: All groups
Not for motor type: -
Min
0
Description:
Sets the parameter filter for commissioning a Terminal Module 150 (TM150).
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Value:
0:
29:
30:
Dependency:
Refer to: p0970
Note:
Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
p0010
TM31 commissioning parameter filter / TM31 comm par_filt
TM31
Can be changed: C2(1), T
Data type: Integer16
P-Group: All groups
Not for motor type: -
Min
0
Description:
Sets the parameter filter for commissioning a Terminal Module 31 (TM31).
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Value:
0:
29:
30:
Dependency:
Refer to: p0970
Note:
Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Ready
Only Siemens int
Parameter reset
Ready
Only Siemens int
Parameter reset
Ready
Only Siemens int
Parameter reset
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
30
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
30
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
30
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
43