Siemens G130 List Manual page 35

Hide thumbs Also See for G130:
Table of Contents

Advertisement

43:
44:
45:
46:
60:
70:
200:
250:
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
EP: Enable Pulses (pulse enable)
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
SS2: Safe Stop 2
STO: Safe Torque Off
r0002
Infeed operating display / INF op_display
B_INF
Can be changed: -
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Operating display for the infeed.
Value:
0:
31:
32:
35:
41:
42:
44:
45:
46:
60:
70:
200:
250:
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
COMM: Commissioning
r0002
TM120 operating display / TM120 op_display
TM120
Can be changed: -
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Operating display for Terminal Module 120 (TM120)
Value:
0:
40:
50:
60:
70:
120:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Switching-on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
Switching-on inhibited - supply STO terminal w/ 24 V (hardware)
Switching-on inhibited - rectify fault, acknowledge fault, STO
Switching-on inhibited - exit commissioning mode (p0009, p0010)
Drive object deactivated/not operational
Initialization
Wait for booting/partial booting
Device signals a topology error
Operation - everything enabled
Ready for switching on - precharging running (p0857)
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
Switching-on inhibited - carry out first commissioning (p0010)
Switching-on inhibited - set "ON/OFF1" = "0" (p0840)
Switching-on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
Switching-on inhibited - connect 24 V to terminal EP (hardware)
Switching-on inhibited - remove fault cause, acknowledge fault
Switching-on inhibited - exit commissioning mode (p0009, p0010)
Infeed deactivated/not operational
Initialization
Wait for booting/partial booting
Device signals a topology error
Module in cyclic operation
Module not in cyclic operation
Alarm
Fault
Initialization
Module deactivated
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
250
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
250
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-