Maintenance Objects
Error Log Entries and Test to Clear Values
Table 570. VC-LEV Error Log Entries
Error
Aux
Type
Data
1 (a)
Any
Notes:
a. The number of VC resources in the system that are in service has fallen
below the calculated minimum value. If the number of in-service VC ports
falls below the MMCH port capacity (value entered in the Minimum
Maintenance Threshold VCs field on the system parameters maintenance
form), a VEC-LEV error is logged. If this outage continues for 15 minutes a
MAJOR alarm is raised. To resolve this alarm, correct the out-of-service
problem by following the procedures below:
1. See
2. If a VC-LEV error/alarm exist and none has been raised against
System Technician-Demanded Tests:
Descriptions and Error Code
There are no System Technician-Demanded test for VC-LEV.
1898
Issue 5 October 2002
Associated Test
Alarm Level
None
MAJOR
''VC-DSPPT''
and
VC-BD or VC-DSPPT maintenance objects, a VC circuit pack may
have been removed from service causing the VC-LEV error/alarm.
To resolve a VC-LEV MAJOR alarm, restore the number of VC ports
available for service to be equal to or more than the calculated port
capacity. See
''Resolving VC-LEV Errors/Alarms''
On/ Off
Board
OFF
''VC-BD''
and resolve any associated alarms.
Test to Clear Value
above for details.