Avaya DEFINITY Server CSI Maintenance Manual page 1824

Table of Contents

Advertisement

Maintenance Objects
Table 539. TEST #1209 DS1 Board Loopback Test — Continued
Error
Test
Code
Result
1039
ABORT
The UDS1 Interface circuit pack is providing timing for the system. Executing
this test could cause major system disruption.
If the UDS1 Interface circuit pack needs to be tested, set the synchronization
reference to another DS1 Interface circuit pack or to the Tone-Clock circuit
pack via the following command sequence:
1950
ABORT
Another loopback/span test is already executing on the DS1 board or the
board is in a network requested loopback mode (Line loopback or Payload
loopback). The hardware error log will indicate whether a Customer Loopback
Jack Test, Far CSU Loopback Test, or the One-Way Span Test is executing or
if the board is in line loopback or payload loopback mode. Only one
long-duration loopback/span test can be active at a given time. Thus, if a
loopback/span test is already active, that test must be terminated via the test
ds1-loop UUCSS end-loopback/span-test command in order to execute
this test.
2000
ABORT
Response to the test was not received within the allowable time period. This
may be due to hyperactivity. Error Type 1538 in the error log indicates
hyperactivity. The hyperactive circuit pack is out of service and one or more of
the following symptoms may be exhibited.
1824
Issue 5 October 2002
Description/ Recommendation
1. Issue the disable synchronization-switch command.
2. Next, issue the set synchronization UUCSS command.
3. Lastly, issue the enable synchronization-switch command.
1. The UDS1-BD tests (such as Test #138 and Test #139) are aborting with
error code 2000.
2. The tests run on the ports of this circuit pack are returning a no board
result.
3. A busyout or a release command has no affect on the test results.
4. A list config command shows that the circuit pack and the ports are
properly installed.
NOTE:
When hyperactivity occurs, the circuit pack is isolated from the system,
and all of the trunks for this circuit pack are placed into the out of
service state. The system will try to restore the circuit pack within 15
minutes. When no faults are detected for 15 minutes, the UDS1
interface circuit pack is restored to normal operation. All of the trunks
for the UDS1 interface circuit pack are then returned to the in service
state. Hyperactivity is often caused by the associated facility. In such a
case, faults (such as slips, misframes, or blue alarms) would be
entered in the error log. In addition, many hardware errors would be
logged against the associated trunk circuits. If the facility is OK and the
error occurs again after 15 minutes, replace the circuit pack.
Continued on next page