PNC-DUP (PNC Duplication)
s. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_HW. Use status
pnc to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20203
points to port network 4.) List config port-network gives the cabinet
number associated with a port network.
t. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_PER. Use status
pnc to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20303
points to port network 4.) List config port-network gives the cabinet
number associated with a port network.
u. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_DS1. Use status
pnc to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20403
points to port network 4.) List config port-network gives the cabinet
number associated with a port network.
v. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_BFD. Use status
pnc to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20203
points to port network 4.) List config port-network gives the cabinet
number associated with a port network.
w. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_SNIL. Use status
pnc to look at the state of health indexes for the PNCs, and investigate any
associated alarms. The last two digits of the error code indicate the
fiber-link number (01-27) of the fiber that reported the retired alarm. List
fiber-link gives the location of the fiber.
x. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_SNIHW. Use
status pnc to look at the state of health indexes for the PNCs, and
investigate any associated alarms. The last two digits of the error code
indicate the fiber-link number (01-27) of the fiber that reported the retired
alarm. List fiber-link gives the location of the fiber.
y. A spontaneous PNC interchange took place in response to the occurrence
of a major or minor alarm on the B-PNC associated with fault class FC_
EAL. This indicates that one or more Expansion Archangel Links are
down. Investigate any EXP-PN alarms. Adding 1 to the last two digits of
the error code gives the PN number of the port network that reported the
alarm. (21003 points to port network 4.) List config port-network gives
the cabinet number associated with a port network.
555-233-143
Issue 1 May 2002
8-1299