POWER
Table 8-524. Test #5 Battery and Battery Charger Query Test — Continued
Error
Test
Code
Result
Description / Recommendation
2029,
ABORT
Internal system error
2319,
1. Retry the command at 1-minute intervals up to 5 times.
2320,
2500
2
FAIL
The system is in nominal power holdover, and the battery is currently so low
that the system will disconnect power very shortly.
1. If power returns, then the port carriers in the PN should power-up again.
2. If power does not return, the system will shut down to prevent damage to
4
FAIL
The battery is currently being charged.
1. After 30 hours, the battery should be fully charged, and this error should
555-233-143
Every circuit pack should be reinserted, and the system should continue
to operate normally. There will probably be a minor alarm against battery
and battery charger due to the fact that the batteries are recharging.
the batteries. Restore power, and the system will reboot. No manual
intervention is required. 3) Rerun the test. If the test still fails, then the
PN's MAINT (Maintenance) circuit pack could be reporting this condition
incorrectly. Resolve every alarm on this MO, and rerun the test. There
are failures that can occur on the PN's Maintenance circuit pack that will
not be detected by their respective maintenance, but which will cause
many, if not every, environment tests to fail. If many environment tests
are failing, the suspect circuit pack, depending on the system
configuration, should be replaced and the test rerun.