POWER
Battery and Battery Charger Query Test (#5)
This test queries the PN's Maintenance circuit pack for the status of the battery
pack and battery charger, and reports the result. In a DC-powered system, this
test should never fail. During this test, the status LED on the battery charger is lit
and extinguished if the status of the battery charger is reported as normal. This
event is a result of checking that the battery charger is connected.
Table 8-526. Test #5 Battery and Battery Charger Query Test
Error
Test
Code
Result
Description / Recommendation
1000
ABORT
System resources required to run this test are not available.
1005
ABORT
Battery charger is not connected. DC-powered cabinets do not have battery
backup; ignore this error.
2000
ABORT
Response to the test request was not received within the allowable time period.
2028
ABORT
Internal system error prevented the extinguishing of the Battery Charger status
LED.
1. Since this test is not relevant for DC-powered systems, an occurrence of
2029,
ABORT
Internal system error
2319,
1. Try the command again at 1-minute intervals up to 5 times.
2320,
2500
any
FAIL
The PN's Maintenance circuit pack is incorrectly reporting a problem with
power. If this test fails for a DC-powered cabinet, the circuit pack has a
problem. Replace the suspect circuit pack, and run the test again.
PASS
All that can be inferred is that an MCC PN's Maintenance circuit pack is
working properly for this test.
555-233-143
this error indicates possible existence of internal system problems.
Issue 1 May 2002
8-1313