I2t in_value s_src
p3240[C]
(r1641)
Perm I2t cont val
10.00...200.00 [%]
p3241[D] (100.00)
<1> The following is valid for activation:
The function module "Extended messages/monitoring” must be activated (r0108.17 = 1).
The maximum duration must be set to a value exceeding zero (p3242 > 0).
A separately-excited synchronous motor (SESM) is used.
<2> p3242 (setting example):
It should be possible to use 150 % of the input variable for a duration of 3 s at a permissible continuous rating
of p3241 = 110 %.
p3242 = ((150 x 150 - 110 x 110) / ((100 + 110) x (100 + 110) - 110 + 110) x 3 s = 0.975 s
1
2
DO: VECTOR
Signals and monitoring functions - Freely parameterizable I2t monitoring (SESM)
I2t max_dur
0.00...3600.00 [s]
p3242[D] (0.00)
200 %
<1>
<2>
+
0.0
3
4
I2t alarm thresh
0.00...99.90 [%]
p3243[D] (50.00)
1
A07823
"I2t monitoring alarm threshold exceeded"
0
I2t alarm threshold exceeded (only SESM)
100 %
1
F07824
"I2t monitoring fault threshold exceeded"
0
I2t fault threshold exceeded (only SESM)
Act I2t integ_val [%]
r3244
5
6
Function diagram
fp_8022_54_eng.vsd
S120/S150/G130/G150
01.06.16 V04.08.00
p0115[6] (4000.00 μs)
r2199.13
[2537.7]
r2199.14
[2537.7]
SESM: Separately-excited synchronous motor
7
8
- 8022 -