VLT AutomationDrive FC 301/302
Programming Guide
Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This parameter is avail-
able when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM, that is, the parameter is valid for PM and non-salient
SPM motors only.
Parameter 1-29 Automatic Motor Adaptation
Table 83: Parameter 1-29 Automatic Motor Adaptation (AMA)
1-29 Automatic Motor Adaptation (AMA)
Default value: [0] Off
Conversion index: –
This parameter cannot be adjsuted while the motor is running.
The AMA function optimizes dynamic motor performance by automatically optimizing the advanced motor parameters (parameter
1-30 Stator Resistance (Rs) to parameter 1-35 Main Reactance (Xh)) on a cold motor at standstill. Activate the AMA function by press-
ing [Hand On] after selecting [1] Enable Complete AMA or [2] Enable Reduced AMA. If an LC filter is used between the drive and the
motor, always select [2] Enable Reduced AMA. See also the section Automatic Motor Adaptation in the Design Guide. After a normal
sequence, the display reads: Press [OK] to finish AMA. After pressing [OK], the drive is ready for operation.
Ensure that a value is set in parameter 14-43 Motor Cosphi before running AMA II.
Op-
Name
Description
tion
[0]*
Off
[1]
Enable
Performs
complete
AMA of the stator resistance R
AMA
The rotor resistance R
The stator leakage reactance X
The rotor leakage reactance X
The main reactance X
Do not select this option if an LC filter is used between the drive and the motor. For best performance, it is
recommended to obtain the advanced motor data from the motor manufacturer to enter into parameter
1-31 Rotor Resistance (Rr) through parameter 1-36 Iron Loss Resistance (Rfe). Complete AMA cannot be per-
formed on permanent magnet motors.
[2]
Enable Re-
Performs a reduced AMA of the stator resistance R
duced AMA
asynchronous motors and non-salient PM motors.
[3]
Enable re-
Performs AMA of the stator resistance R
duced AMA
leakage reactance X
II
[4]
Enable re-
Performs a reduced AMA of the stator resistance R
duced AMA
used between the drive and the motor. The AMA II is a variant of AMA, based on the principles of the tor-
II
que calibration. It is recommended for special motors (for example S3) and high-power motors.
[5]
Enable ro-
Performs rotation with 60% of nominal speed in Flux Sensorless with soft PID independent of selection in
tating AMA
parameter 1-01 Motor Control Principle. Measures Back EMF on PM motors and re-measures main reactance
II
Danfoss A/S © 2022.12
Parameter type: Option
Data type: Uint8
N O T I C E
N O T I C E
s
r
1
, and
2
h
, the rotor resistance R
s
, and the main reactance X
21
Setup: All setups
Change during operation: False
in the system only. This option is available for standard
s
, the stator leakage reactance X
r
.
h
in the system only. Select this option if an LC filter is
s
AU275636650261en-000101 / 130R0334 | 79