Parameter 15-13 Logging Mode
Table 772: Parameter 15-13 Logging Mode
15-13 Logging Mode
Default value: [0] Log always
Conversion index: -
Option
Name
[0]*
Log always
[1]
Log once on trigger
Parameter 15-14 Samples Before Trigger
Table 773: Parameter 15-14 Samples Before Trigger
15-14 Samples Before Trigger
Default value: 50
Conversion index: 0
Before a trigger event, enter the percentage of all samples which should be retained in the log. See also parameter 15-12 Trigger
Event and parameter 15-13 Logging Mode.
Danfoss A/S © 2022.12
Description
This option is only available in FC 302.
Parameter type: Option
Data type: Uint8
Description
Select [0] Log always for continuous logging.
Select [1] Log once on trigger to start and stop logging conditionally using parameter 15-12 Trig-
ger Event and parameter 15-14 Samples Before Trigger.
Parameter type: Range, 0 - 100
Data type: Uint8
Parameter Descriptions
N O T I C E
Setup: 2 setups
Change during operation: True
Setup: 2 setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 483