Parameter 4-21 Speed Limit Factor Source
Table 272: Parameter 4-21 Speed Limit Factor Source
4-21 Speed Limit Factor Source
Default value: [0] No function
Conversion index: –
Select an analog input for scaling the settings in parameter 4-19 Max Output Frequency 0–100% (or the other way around). The signal
levels corresponding to 0% and 100% are defined in the analog input scaling, for example parameter group 6-1* Analog Input 1. This
parameter is only active when parameter 1-00 Configuration Mode is in [4] Torque Open Loop.
Option
[0]*
[2]
[4]
[6]
[8]
[10]
[12]
[14]
[16]
Parameter 4-23 Brake Check Limit Factor Source
Table 273: Parameter 4-23 Brake Check Limit Factor Source
4-23 Brake Check Limit Factor Source
Default value: [0] DC-link Voltage
Conversion index: –
Danfoss A/S © 2022.12
Name
No function
Analog in 53
Analog in 53 inv
Analog in 54
Analog in 54 inv
Analog in X30-11
Analog in X30-11 inv
Analog in X30-12
Analog in X30-12 inv
Parameter type: Option
Data type: Uint8
Name
No function
Analog in 53
Analog in 53 inv
Analog in 54
Analog in 54 inv
Analog in X30-11
Analog in X30-11 inv
Analog in X30-12
Analog in X30-12 inv
Parameter type: Option
Data type: Uint8
Parameter Descriptions
Description
Setup: All setups
Change during operation: True
Description
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 157