VLT AutomationDrive FC 301/302
Programming Guide
Option
Name
[229]
Vir. master on ref.
[231]
In power lim. mot.
[232]
In power lim. gen.
[233]
In power limit
[234]
PE power off
[246]
Emcy mode was act.
[247]
Emergency mode
[249]
Emcy m. OPR un-
exptected
[250]
Emcy mode limits
[254]
Testing emcy mode
Parameter 5-41 On Delay, Relay
Table 362: Parameter 5-41 On Delay, Relay
5-41 On Delay, Relay
Default value: 0.01 s
Conversion index: -2
Enter the delay of the relay cut in time. Select 1 of 2 internal mechanical relays in an array function. See parameter 5-40 Function
Relay for details.
216 | Danfoss A/S © 2022.12
Description
This option is available only with software version 48.XX.
The virtual master is running on the set reference.
This option is only available in FC 302.
This option is only available in FC 302.
This option is only available in FC 302.
The drive has been operating in emergency mode.
The drive is operating in emergency mode. See parameter group 24-0* Emergency Mode.
Emergency mode is not operating as expected, for example, live zero monitoring on an analog
input is activated.
During emergency mode operation, 1 of the critical alarms has been activated and suppressed
by emergency mode. This may lead to reduced drive performance and expected lifetime before
service is required.
Emergency mode was activated in a special test mode where the drive stops on all alarms.
Parameter type: Range, 0.01 – 600 s, Array [9]
Data type: Uint16
N O T I C E
N O T I C E
N O T I C E
N O T I C E
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334