Danfoss VLT AutomationDrive FC 301 Programming Manual page 218

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Ref.
(RPM)
High
ref.
value
P 5-53/
p 5-58
Low
ref.
value
P 5-52/
p 5-57
Low freq.
P 5-50/
P 5-55
Illustration 65: Pulse Input
Parameter 5-50 Term. 29 Low Frequency
Table 364: Parameter 5-50 Term. 29 Low Frequency
5-50 Term. 29 Low Frequency
Default value: 100 Hz
Conversion index: 0
Enter the low frequency limit corresponding to the low motor shaft speed (that is low reference value) in parameter 5-52 Term. 29
Low Ref./Feedb. Value. Refer to
Parameter 5-51 Term. 29 High Frequency
Table 365: Parameter 5-51 Term. 29 High Frequency
5-51 Term. 29 High Frequency
Default value: Size related
Conversion index: 0
Enter the high frequency limit corresponding to the high motor shaft speed (that is high reference value) in parameter 5-53 Term. 29
High Ref./Feedb. Value.
Parameter 5-52 Term. 29 Low Ref./Feedb. Value
Table 366: Parameter 5-52 Term. 29 Low Ref./Feedb. Value
5-52 Term. 29 Low Ref./Feedb. Value
Default value: Size related
Conversion index: -3
Enter the low reference value limit for the motor shaft speed [RPM]. This is also the lowest feedback value, see also parameter 5-57
Term. 33 Low Ref./Feedb. Value. Set terminal 29 to digital input (parameter 5-02 Terminal 29 Mode = [0] Input (default) and parameter
5-13 Terminal 29 Digital Input = applicable value).
218 | Danfoss A/S © 2022.12
High freq.
P 5-51/
P 5-56
Parameter type: Range, 0 – 110000 Hz
Data type: Uint32
Illustration
65.
Parameter type: Range, 0 – 110000 Hz
Data type: Uint32
Parameter type: Range, -999999.999 - 999999.999 Reference- Feed-
backUnit
Data type: Int32
Input
(Hz)
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Parameter Descriptions
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334