Parameter 13-11 Comparator Operator
Table 675: Parameter 13-11 Comparator Operator
13-11 Comparator Operator
Default value: Size related
Conversion index: -
Select the operator to be used in the comparison. This is an array parameter containing comparator operators 0–5.
Op-
Name
Description
tion
[0]
<
The result of the evaluation is true when the variable selected in parameter 13-10 Comparator Operand
is smaller than the fixed value in parameter 13-12 Comparator Value. The result is false if the variable
selected in parameter 13-10 Comparator Operand is greater than the fixed value in parameter 13-12
Comparator Value.
≂ (equal)
[1]
The result of the evaluation is true when the variable selected in parameter 13-10 Comparator Operand
is approximately equal to the fixed value in parameter 13-12 Comparator Value.
Danfoss A/S © 2022.12
Description
This option is only available with software version 48.2X and newer.
The position error exceeds the value in parameter 4-71 Maximum Position Error for the time set
in parameter 4-72 Position Error Timeout.
This option is only available with software version 48.2X and newer.
The position is outside the limits set in parameter 3-06 Minimum Position and parameter 3-07
Maximum Position.
This option is only available with software version 48.2X and newer.
Target position is reached in touch probe position mode.
This option is only available with software version 48.2X and newer.
Touch probe positioning is active. The drive monitors the touch probe sensor input.
Parameter type: Option, Array [10]
Data type: Uint8
If [20] Alarm number or [21] Warning number is selected in parameter 3-10 Comparator Operand, [0] <
cannot be selected in this parameter.
N O T I C E
N O T I C E
N O T I C E
N O T I C E
Setup: 2 setups
Change during operation: True
N O T I C E
AU275636650261en-000101 / 130R0334 | 387