VLT AutomationDrive FC 301/302
Programming Guide
Option
[4]
[5]
[8]
[10]
[20]
[30]
Parameter 42-21 Type
Table 1381: Parameter 42-21 Type
42-21 Type
Default Value: [0] NCNC
Conversion Index: -
Option
[0]*
[1]
[2]
[3]
Parameter 42-22 Discrepancy Time
Table 1382: Parameter 42-22 Discrepancy Time
42-22 Discrepancy Time
Default Value: 10 ms
Conversion Index: -3
An adjustable filter time prevents faults caused by temporary discrepancy.
Parameter 42-23 Stable Signal Time
Table 1383: Parameter 42-23 Stable Signal Time
42-23 Stable Signal Time
Default Value: 10 ms
Conversion Index: -3
An adjustable signal filter in the safety option suppresses temporary signal changes using test pulse pattern.
Parameter 42-24 Restart Behaviour
Table 1384: Parameter 42-24 Restart Behaviour
42-24 Restart Behaviour
Default value: [0] Manual
Conversion index: -
Danfoss A/S © 2022.12
Name
SLS-b
Disable
SO mon
None
Internal event OK
No function
Parameter Type: Option
Data Type: Uint8
Name
NCNC
Antivalent
NC
NO
Parameter Type: Range, 0 - 5000 ms
Data Type: Uint16
Parameter Type: Range, 0 - 5000 ms
Data Type: Uint16
Parameter type: Option
Data type: Uint8
Parameter Descriptions
Description
Setup: All setups
Change during operation: False
Description
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: False
AU275636650261en-000101 / 130R0334 | 671