VLT AutomationDrive FC 301/302
Programming Guide
Parameter 24-07 Emergency Mode Feedback Source
Table 1044: Parameter 24-07 Emergency Mode Feedback Source
24-07 Emergency Mode Feedback Source
Default value: [0] No function
Conversion index: -
In emergency mode closed-loop operation, feedback is requested for the internal PID controller. Select the feedback input to be
used for the feedback signal.
Option
Name
[0]*
No function
[1]
Analog input 53
[2]
Analog input 54
[3]
Frequency input 29
[4]
Frequency input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[16]
Analog input X49/1
[17]
Analog input X49/3
[18]
Analog input X49/5
[99]
Normal feedback
Parameter 24-09 Emergency Mode Alarm Handling
Table 1045: Parameter 24-09 Emergency Mode Alarm Handling
24-09 Emergency Mode Alarm Handling
Default value: [1] Trip, critical alarms
Conversion index: -
Warranty-affecting alarms. Certain alarms can affect the lifetime of the drive. Should 1 of these ignored alarms occur while in
emergency mode, the alarms are logged and stored in the emergency-mode log.
The setting in parameter 14-20 Reset Mode is disregarded if emergency mode is active (see parameter group 24-0* Emergency
Mode).
Select an option to define the response to alarms when emergency mode is active and an alarm is issued.
568 | Danfoss A/S © 2022.12
Parameter type: Option
Data type: Uint8
Description
This option is only available in FC 302.
Parameter type: Option
Data type: Uint8
N O T I C E
N O T I C E
Parameter Descriptions
Setup: All setups
Change during operation: True
N O T I C E
Setup: 2 setups
Change during operation: False