Danfoss VLT AutomationDrive FC 301 Programming Manual page 563

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
The following events are logged:
W200 - Emergency mode.
W201 - Emerg. M mode was act. (deactivated).
W202 - Emerg. M limits exceeded covered by the activated critical alarm number.
(W280) - Emcy M service warning - service is needed.
(W281) - Emcy OPR unexpected - emergency mode does not work as expected.
All alarms are logged as usual, and critical emergency mode alarms are logged in the emergency mode log in parameter group 18-1*
Emergency Mode Log.
During emergency-mode operation, all stop commands to the drive are ignored, including coast/coast inverse and external inter-
lock. The keypad is also locked during emergency mode to prevent user interference during operation of the safety system. How-
ever, if Safe Torque Off is available in the drive, this function is still active.
Emergency mode has a special live zero function for handling lost analog signal inputs used for emergency mode setpoint/feed-
back, for example, for handling a burnt cable. How emergency mode should continue in these live zero situations is configured in
parameter 6-02 Emergency Mode Live Zero Timeout Function. If live zero is activated, Emergency mode not working as expected is
activated so that a redundant system can take over or a setup change can be activated. A warning for live zero has a higher
priority than the warning Emergency mode and will replace that information in the display.
If setting the command [11] Start Reversing on a digital input terminal in parameter 5-10 Terminal 18 Digital Input, the drive under-
stands this as a reversing command.
Parameter 24-00 Emergency Mode Function
Table 1037: Parameter 24-00 Emergency Mode Function
24-00 Emergency Mode Function
Default value: [0] Disabled
Conversion index: -
Alarms are produced or ignored in accordance with the selection in parameter 24-09 Emergency Mode Alarm Handling.
Option
Name
[0]*
Disabled
[1]
Enabled-run for-
ward
[2]
Enable-run re-
verse
[3]
Enabled-coast
[4]
Enable-run
Fwd/Rev
[8]
Alarm suppres-
sion
Danfoss A/S © 2022.12
N O T I C E
N O T I C E
N O T I C E
Parameter type: Option
Data type: Uint8
N O T I C E
Description
The emergency-mode function is not active.
In this mode, the motor continues to operate in a clockwise direction. Works only in open loop.
Set parameter 24-01 Emergency Mode Configuration to [0] Open Loop.
In this mode, the motor continues to operate in a counterclockwise direction. Works only in open
loop. Set parameter 24-01 Emergency Mode Configuration to [0] Open Loop.
In this mode, the output is disabled, and the motor is allowed to coast to stop.
In this mode, the drive continues operation as normal, meaning on standard parameters and con-
trol operation, but where the alarms are suppressed as in normal emergency mode. The emcy LCP
Parameter Descriptions
Setup: 2 setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 563