VLT AutomationDrive FC 301/302
Programming Guide
Parameter 1-29 Automatic Motor Adap-
tation (AMA)
Parameter 3-02 Minimum Reference
Parameter 3-03 Maximum Reference
Parameter 3-41 Ramp 1 Ramp Up Time
Parameter 3-42 Ramp 1 Ramp Down
Time
Parameter 3-13 Reference Site
Another easy way of commissioning the drive is by using the smart application setup (SAS), which can also be found by pressing
[Quick Menu]. To set up the applications listed, follow the instructions on the successive screens.
The [Info] key can be used throughout the SAS to see help information for various selections, settings, and messages. The following
3 applications are included:
•
Mechanical brake.
•
Conveyor.
•
Pump/fan.
The following 4 fieldbusses can be selected:
•
PROFIBUS.
•
PROFINET.
•
DeviceNet.
•
EtherNet/IP.
The drive ignores the start conditions when SAS is active.
Danfoss A/S © 2022.12
Set desired AMA function. Enable
complete AMA is recommended.
Set the minimum speed of the
motor shaft.
Set the maximum speed of the
motor shaft.
Set the ramp-up time with refer-
ence to synchronous motor
speed, n
.
s
Set the ramp-down time with ref-
erence to synchronous motor
speed, n
.
s
Set the site from where the refer-
ence must work.
N O T I C E
How to Program
AU275636650261en-000101 / 130R0334 | 27