VLT AutomationDrive FC 301/302
Programming Guide
5.16.5 16-6* Inputs and Outputs
The following parameters are only available in FC 302:
-
Parameter 16-67 Freq. Input #29 [Hz]
-
Parameter 16-70 Pulse Output #29 [Hz]
Parameter 16-60 Digital Input
Table 873: Parameter 16-60 Digital Input
16-60 Digital Input
Default value: 0
Conversion index: 0
View the signal states from the active digital inputs. Example: Input 18 corresponds to bit number 5, 0 = no signal, 1 = connected
signal. Bit 6 works in the opposite way, on = 0, off = 1 (Safe Torque Off input).
Table 874: Active Digital Inputs
Bit
Input
0
Digital input terminal 33.
1
Digital input terminal 32.
2
Digital input terminal 29.
3
Digital input terminal 27.
4
Digital input terminal 19.
5
Digital input terminal 18.
6
Digital input terminal 37.
7
Digital input VLT® General Purpose I/O MCB 101 terminal X30/4.
8
Digital input VLT® General Purpose I/O MCB 101 terminal X30/3.
9
Digital input VLT® General Purpose I/O MCB 101 terminal X30/2.
Bit 10–63
Reserved for future terminals.
Danfoss A/S © 2022.12
N O T I C E
Parameter type: Range, 0 - 65535
Data type: Uint16
Parameter Descriptions
Setup: All setups
Change during operation: False
AU275636650261en-000101 / 130R0334 | 507