Danfoss VLT AutomationDrive FC 301 Programming Manual page 373

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Start
event P13-01
State 1
13-51.0
13-52.0
Stop
event P13-02
State 4
13-51.3
13-52.3
Illustration 78: Example of Events and Actions
Starting and stopping the SLC
Start and stop the SLC by selecting [1] On or [0] Off in parameter 13-00 SL Controller Mode. The SLC always starts in state 0 (where it
evaluates event [0]). The SLC starts when the start event (defined in parameter 13-01 Start Event) is evaluated as true (provided that
[1] On is selected in parameter 13-00 SL Controller Mode). The SLC stops when the stop event (parameter 13-02 Stop Event) is true.
Parameter 13-03 Reset SLC resets all SLC parameters and starts programming from scratch.
SLC is only active in auto-on mode, not hand-on mode.
5.13.1 13-0* SLC Settings
Use the SLC settings to activate, deactivate, and reset the smart logic control sequence. The logic functions and comparators are
always running in the background, which opens for separate control of digital inputs and outputs.
Parameter 13-00 SL Controller Mode
Table 670: Parameter 13-00 SL Controller Mode
13-00 SL Controller Mode
Default value: Size related
Conversion index: -
An array with 4 elements [0]–[3] is shown in the display.
Option
Name
[0]
Off
[1]
On
Parameter 13-01 Start Event
Table 671: Parameter 13-01 Start Event
13-01 Start Event
Default value: Size related
Conversion index: -
Select the boolean (true or false) input to activate smart logic control.
Danfoss A/S © 2022.12
State 2
13-51.1
13-52.1
Stop
event P13-02
State 3
13-51.2
13-52.2
Stop
event P13-02
N O T I C E
Parameter type: Option, Array [4]
Data type: Uint8
Description
Disables the smart logic controller.
Enables the smart logic controller.
Parameter type: Option, Array [4]
Data type: Uint8
Parameter Descriptions
Setup: 2 setups
Change during operation: True
Setup: 2 setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 373