VLT AutomationDrive FC 301/302
Programming Guide
Op-
Name
Description
tion
[0]*
Clear at
Homing Ok is cleared at power-up and a new homing is needed for subsequent positioning operations.
power-up
The option is a typical selection when using incremental encoder and the position tracking is lost at pow-
er-down only.
[1]
Clear at
Homing Ok is cleared at every motor coast and a new homing is needed. The option is a typical selection
coast
for sensorless control as position tracking is lost when motor is coasted.
[2]
Clear at
Homing Ok is cleared at motor coast only while motor is running and a new homing is needed. The option
coast run-
is a typical selection for sensorless control with a mechanical brake holding the position at stand still.
ning
[3]
Clear at
Homing Ok is only cleared at new start of the selected homing function. The option is a typical selection
homing on-
for absolute encoders. After completing the selected homing function parameter 17-74 Position Offset is
ly
automatically set to the offset calculated by: Parameter 17-74 Position Offset = (Parameter 17-82.0 Home
Position) - (Position value read from encoder). Start a new homing to re-calculate Parameter 17-74 Position
Offset, for example, after replacing the encoder.
Parameter 17-87 Homing Activation
Table 957: Parameter 17-87 Homing Activation
17-87 Homing Activation
Default value: [0] Manual
Conversion index: -
This parameter is only available with software version 48.XX.
Activation manner of drive homing and master homing. Master homing can be activated by a Set Master Home signal or the Start
Homing signal by selecting options [2] Manual and Master and [3] Auto and Master.
Op-
Name
Description
tion
[0]*
Manual
Activates homing function selected in parameter 17-80 Homing Function using the Start Homing signal.
[1]
Auto
Homing function selected in parameter 17-80 Homing Function is activated automatically when the
Homing OK signal is low and start signal is applied.
[2]
Manual and
Activates homing function selected in parameter 17-80 Homing Function and sets the actual master po-
master
sition as defined in parameter 17-88 Master Home Position, using Start Homing signal.
[3]
Auto and
Homing function selected in parameter 17-80 Homing Function is activated automatically when the
master
Homing OK signal is low and start signal is applied. The actual master position is set as defined in pa-
rameter 17-88 Master Home Position.
Parameter 17-88 Master Home Position
Table 958: Parameter 17-88 Master Home Position
17-88 Master Home Position
Default value: 0 Custom- ReadoutUnit2
Conversion index: 0
Danfoss A/S © 2022.12
Parameter type: Option
Data type: Uint8
N O T I C E
Parameter type: Range, -2147483648 - 2147483647
CustomReadoutUnit2
Data type: Int32
Parameter Descriptions
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 533