Danfoss VLT AutomationDrive FC 301 Programming Manual page 232

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
for a time period defined in parameter 6-00 Live Zero Timeout Time, then the function set in parameter 6-01 Live Zero Timeout Function
is activated. If several timeouts occur simultaneously, the drive prioritizes the timeout functions as follows:
Parameter 6-01 Live Zero Timeout Function
Parameter 8-04 Control Word Timeout Function
Option
Name
[0]*
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[20]
Coast
[21]
Coast and trip
Parameter 6-02 Emergency Mode Live Zero Timeout Function
Table 399: Parameter 6-02 Emergency Mode Live Zero Timeout Function
6-02 Emergency Mode Live Zero Timeout Function
Default value: [0] Off
Conversion index: –
Select the timeout function when emergency mode is active. The function set in this parameter is activated if the input signal on
analog inputs is below 50% of the low value for a period defined in parameter 6-00 Live Zero Timeout Time.
Option
Name
[0]*
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
5.7.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
232 | Danfoss A/S © 2022.12
Description
Frozen at the present value.
Overruled to stop.
Overruled to jog speed.
Overruled to maximum speed.
Overruled to stop with subsequent trip.
Parameter type: Option
Data type: Uint8
Description
Frozen at the present value.
Overruled to stop.
Overruled to jog speed.
Overruled to maximum speed.
Parameter Descriptions
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents