VLT AutomationDrive FC 301/302
Programming Guide
Option
Name
Description
[0]*
Do not reset
Retains the setup specified in parameter 8-04 Control Word Timeout Function, following a control word
timeout.
[1]
Do reset
Restores the drive to the original setup following a control word timeout. The drive resets and then im-
mediately reverts to the [0] Do not reset setting.
Parameter 8-07 Diagnosis Trigger
Table 501: Parameter 8-07 Diagnosis Trigger
8-07 Diagnosis Trigger
Default value: [0] Disable
Conversion index: –
This parameter has no function for DeviceNet.
Option
[0]*
[1]
[2]
Parameter 8-08 Readout Filtering
Table 502: Parameter 8-08 Readout Filtering
8-08 Readout Filtering
Default value: Size related
Conversion index: –
Use this function if the speed feedback value readouts on the fieldbus fluctuate. Select [1] Motor Data LP-Filter if the function is
required. A power cycle is required for changes to take effect.
Option
Name
[0]
Motor data Std-Filt.
[1]
Motor data LP-Filter
274 | Danfoss A/S © 2022.12
Parameter type: Option
Data type: Uint8
Name
Disable
Trigger on alarms
Trigger alarm/warn.
Parameter type: Option, Array [1]
Data type: Uint8
Description
Normal fieldbus readouts.
Filtered fieldbus readouts of the following parameters:
Parameter 16-10 Power [kW]
Parameter 16-11 Power [hp]
Parameter 16-12 Motor Voltage
Parameter 16-14 Motor current
Parameter 16-16 Torque [Nm]
Parameter 16-17 Speed [RPM]
Parameter 16-22 Torque [%]
Parameter 16-25 Torque [Nm] High
Parameter Descriptions
Setup: 2 setups
Change during operation: True
Description
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334