Parameter 12-99 Media Counters
Table 669: Parameter 12-99 Media Counters
12-99 Media Counters
Default value: 0
Conversion index: 0
This parameter is read-only. Advanced interface counters from a built-in switch can be used for low-level troubleshooting. The pa-
rameter shows a sum of port 1 + port 2.
5.13 Parameter Group 13-** Smart Logic Control
Smart logic control (SLC) is a sequence of user-defined actions (see parameter 13-52 SL Controller 1 Action) executed by the SLC when
the associated user-defined event (see parameter 13-51 SL Controller 1 Event) is evaluated as true by the SLC. The condition for an
event can be a particular status, or that the output from a logic rule or a comparator operand becomes true. That leads to an associ-
ated action as illustrated:
Par. 13-51
SL Controller Event
Running
Warning
Torque limit
Digital input X 30/2
. . .
Par. 13-43
Logic Rule Operator 2
. . .
. . .
Par. 13-11
Comparator Operator
=
TRUE longer than..
. . .
. . .
Illustration 77: Smart Logic Control (SLC)
Events and actions are each numbered and linked in pairs (states). This means that when the 1
st
1
action is executed. After this, the conditions of the 2
so on. Only 1 event is evaluated at any time. If an event is evaluated as false, nothing happens (in the SLC) during the current scan
interval and no other events are evaluated. This means that when the SLC starts, it evaluates the 1
each scan interval. Only when the 1
It is possible to program 1–20 events and actions. When the last event/action has been executed, the sequence starts over again
st
from the 1
event/action.
Four concurring sequences can be defined with each up to 20 event and action pairs. The sequences are executed at the same time
but operate separately. For example, sequence 1 may have executed 3 actions, while sequence 2 still waits for its 1
In this example, parameter 13-00 SL Controller Mode [0], parameter 13-01 Start Event [1], and parameter 13-02 Stop Event [2] corre-
spond to sequence 1, sequence 2, sequence 3, and the like.
Comparators Flip-Flops, timers, and logic rules are shared between sequences.
372 | Danfoss A/S © 2022.12
Parameter type: Range, 0 - 4294967295
Data type: Uint32
Par. 13-52
SL Controller Action
Coast
Start timer
Set Do X low
Select setup 2
. . .
nd
event are evaluated and if evaluated true, the 2
st
event is evaluated as true, the SLC executes the 1
N O T I C E
Parameter Descriptions
Setup: All setups
Change during operation: True
st
event is fulfilled (becomes true), the
nd
action is executed, and
st
event (and only the 1
st
action and starts evaluating the 2
st
AU275636650261en-000101 / 130R0334
st
event) in
nd
event.
event to occur.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents