VLT AutomationDrive FC 301/302
Programming Guide
Ref./Feedback
[RPM]
Par 6-xx
1500
'High Ref./
Feedb. Value'
1200
900
600
300
Par 6-xx
'Low Ref./
150
Feedb. Value'
Ex.
1 V
Par 6-xx
'Low Voltage'or
'Low Current'
Illustration 69: Analog Input 1
Parameter 6-10 Terminal 53 Low Voltage
Table 400: Parameter 6-10 Terminal 53 Low Voltage
6-10 Terminal 53 Low Voltage
Default value: Size related
Conversion index: -2
Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value set in parameter
6-14 Terminal 53 Low Ref./Feedb. Value.
Parameter 6-11 Terminal 53 High Voltage
Table 401: Parameter 6-11 Terminal 53 High Voltage
6-11 Terminal 53 High Voltage
Default value: 10 V
Conversion index: -2
Enter the high voltage value. This analog input scaling value should correspond to the high reference feedback value set in parame-
ter 6-15 Terminal 53 High Ref./Feedb. Value.
Parameter 6-12 Terminal 53 Low Current
Table 402: Parameter 6-12 Terminal 53 Low Current
6-12 Terminal 53 Low Current
Default value: 0.14 mA
Conversion index: -5
Enter the low current value. This reference signal should correspond to the minimum reference value, set in parameter 3-02 Mini-
mum Reference. Set the value to exceed 2 mA to activate the live zero timeout function in parameter 6-01 Live Zero Timeout Function.
Parameter 6-13 Terminal 53 High Current
Table 403: Parameter 6-13 Terminal 53 High Current
6-13 Terminal 53 High Current
Default value: 20 mA
Conversion index: -5
Enter the high current value corresponding to the high reference/feedback set in parameter 6-15 Terminal 53 High Ref./Feedb. Value.
Danfoss A/S © 2022.12
5 V
10 V
Par 6-xx
Analog input
'High Voltage'or
'High Current'
Parameter type: Range, -10.00 - par. 6-11 V
Data type: Int16
Parameter type: Range, par. 6-10 V - 10 V
Data type: Int16
Parameter type: Range, par. 0 - par. 6-13 mA
Data type: Int16
Parameter type: Range, par. par. 6-12 mA - 20 mA
Data type: Int16
Parameter Descriptions
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 233