Danfoss VLT AutomationDrive FC 301 Programming Manual page 67

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Use this parameter to configure the drive for either high or normal overload. When selecting the drive size, always review the tech-
nical data in the Operating Guide or the Design Guide to know the available output current.
Option
Name
[0]
High torque
[1]
Normal torque
Parameter 1-05 Local Mode Configuration
Table 63: Parameter 1-05 Local Mode Configuration
1-05 Local Mode Configuration
Default value: [2] As mode par. 1-00
Conversion index: –
Select which application configuration mode (parameter 1-00 Configuration Mode), that is application control principle, to use when
a local (LCP) reference is active. A local reference can be active only when parameter 3-13 Reference Site is set to [0] Linked to Hand/
Auto or [2] Local. By default the local reference is active in hand-on mode only.
Option
Name
[0]
Speed open loop
[1]
Speed closed loop
[2]*
As mode par. 1-00
[4]
Positioning
Parameter 1-06 Clockwise Direction
Table 64: Parameter 1-06 Clockwise Direction
1-06 Clockwise Direction
Default value: [0] Normal
Conversion index: –
This parameter cannot be adjusted while the motor is running.
This parameter defines the term clockwise corresponding to the LCP direction arrow. Used for easy change of direction of shaft
rotation without swapping motor wires.
Option
Name
Description
[0]*
Normal
The motor shaft turns in clockwise direction when the drive is connected U⇒U, V⇒V, and W⇒W to the
motor.
[1]
Inverse
The motor shaft turns in counterclockwise direction when the drive is connected U⇒U, V⇒V, and W⇒W
to the motor.
[2]
Inverse all
Danfoss A/S © 2022.12
Description
Allows up to 160% overtorque.
For oversized motor. Allows up to 110% overtorque.
Parameter type: Option
Data type: Uint8
Description
Allows up to 160% overtorque.
Parameter type: Option
Data type: Uint8
N O T I C E
Parameter Descriptions
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: False
AU275636650261en-000101 / 130R0334 | 67