VLT AutomationDrive FC 301/302
Programming Guide
5.12.4 12-3* EtherNet/IP
Parameter 12-30 Warning Parameter
Table 628: Parameter 12-30 Warning Parameter
12-30 Warning Parameter
Default value: 0
Conversion index: 0
This parameter is read-only. It shows the EthetNet/IP-specific 16-bit status word.
Table 629: 16-Bit Status Word, EtherNet/IP
Bit
Description
0
Owned
1
Not used
2
Configured
3
Not used
4
Not used
5
Not used
6
Not used
7
Not used
8
Minor recoverable fault
9
Minor unrecoverable fault
10
Major recoverable fault
11
Major unrecoverable fault
12
Not used
13
Not used
14
Not used
15
Not used
Parameter 12-31 Net Reference
Table 630: Parameter 12-31 Net Reference
12-31 Net Reference
Default value: [0] Off
Conversion index: –
Shows the reference source in instance 21/71.
Option
[0]*
[1]
Danfoss A/S © 2022.12
Parameter type: Range, 0 - 2147483647
Data type: Uint32
Parameter type: Option
Data type: Uint8
Name
Off
On
Setup: All setups
Change during operation: True
Setup: 2 setups
Change during operation: True
Description
AU275636650261en-000101 / 130R0334 | 361
Parameter Descriptions